Tall Atrium Smoke Extraction: Why Exhaust at Mid-Height?

Eng. Mohammad Yacoub Baker · Design notesم. محمد يعقوب بكر · ملاحظات تصميم (المقال باللغة الإنجليزية)

The Four Seasons atrium in Guangzhou IFC runs from L70 to L100. The published engineering paper shows two smoke-extraction points at L81 and two at the top of the atrium.

So why extract at mid-height when smoke rises?

I worked through the numbers with clear assumptions (3 MW design fire, NFPA 92 plume equations):

Keeping L70–L72 clear needs about 61 m³/s. That is achievable.
Keeping everything up to L81 clear needs about 367 m³/s. Keeping every balcony clear needs about 1,900 m³/s. No fan system can do that.
A 3 MW plume may stratify at 59–89 m, below the top exhaust at roughly 110 m. Top-only fans could end up extracting mostly clean air.
At L81 the smoke is about 5× less diluted than at the top, so every m³/s extracted there removes more smoke.

The takeaway: in a tall atrium, fans don't eliminate smoke. They buy time. The real test is ASET > RSET for every floor group, and the published study reports only a 65 s margin for floors 73–92.

Hand calculations tell you where to put the exhaust and how big the problem is. CFD tells you whether the design works.

The full case study (10 pages) is attached to the original LinkedIn post.

These notes are for design discussion. Check them against the codes, data and conditions of your own project.