In one of our projects, glazing was used as part of a required fire separation.
A simple question came up during coordination:
Should the window sprinklers be installed on one side of the glass or on both sides?
Before proceeding, we went back to NFPA 13.
NFPA 13:2019, Section 9.3.15 addresses Sprinkler-Protected Glazing where sprinklers are used with glazing as an alternative to a required fire-rated wall or window assembly.
The code requires listed specific-application window sprinklers, unless standard spray sprinklers are specifically permitted by the building code.
More importantly:
If the assembly is required to be protected from both sides, sprinklers must be installed on both sides of the glazing.
So the real design question is not simply:
Inside or outside?
It is:
From which side can the required fire exposure occur?
For the listed arrangements shown in the figure:
- Interior fire separation: protection can be required on both sides.
- Exterior separation – fire originating from our building: sprinklers can be located on the inside face.
- Exterior exposure – fire originating from an adjacent building: protection can be provided on the outside face.
The final arrangement must follow the applicable building/fire code, approved assembly, AHJ requirements, and sprinkler listing.
What about spacing?
Here we need to distinguish between NFPA requirements and sprinkler listing requirements.
For Exposure Protection, NFPA 13:2019, Section 8.7.9.7.2 limits the maximum spacing between window sprinklers to:
8 ft (2.4 m) maximum, unless listed for a greater distance.
NFPA 13:2019, Section 8.7.8.4 also requires listed window sprinklers to be positioned within 2 in. (50 mm) of the top of the window sash, while the nominal distance from the window is determined by Table 8.7.8.4.
For Sprinkler-Protected Glazing under Section 9.3.15, however, the detailed installation dimensions are controlled by the specific sprinkler listing.
For the listed arrangement shown in the second image:
6 ft (1.83 m) minimum spacing
8 ft (2.44 m) maximum spacing
If the spacing needs to be less than the listed minimum, a suitable baffle or mullion may be required between adjacent sprinklers.
And this creates an important coordination point:
The architectural mullion layout can directly affect the sprinkler layout.
Window Sprinkler design is not simply placing sprinklers beside the glass.
Fire Exposure → Required Side of Protection → Approved/Listed System → Spacing → Glass Distance → Mullions/Baffles → Hydraulic Design
A small architectural decision around glazing can completely change the fire protection arrangement.
References
NFPA 13:2019 — Section 9.3.15
NFPA 13:2019 — Section 8.7.8.4 & Table 8.7.8.4
NFPA 13:2019 — Section 8.7.9.7.2
Specific-Application Window Sprinkler Listing
These notes are for design discussion. Always apply the code edition adopted for your project and confirm with the AHJ.