A Fire Hose Cabinet doesn’t always need a separate piping network.
NFPA 13:2019 permits certain 1½-inch (40 mm) hose connections to be supplied directly from the sprinkler system, subject to specific conditions.
According to Sections 16.15.1.3 and 16.15.1.4:
- Wet Pipe System: Connections for fire purposes only are permitted on wet sprinkler systems.
- Connection Location: Permitted arrangements include sprinkler risers upstream of sprinkler control valves and, under specific conditions, ceiling sprinkler piping.
- Minimum Pipe Size: The sprinkler pipe at the connection point must be at least 2½ inches (65 mm), with an exception for qualifying looped/grid systems.
- FHC Supply Branch: The branch pipe size is determined separately under the applicable code requirements.
- Pressure Regulation: Pressure-regulating devices must be provided where required.
Important distinction: The 65 mm requirement refers to the sprinkler pipe at the connection point, not the 40 mm hose connection inside the FHC.
A separate network isn’t always necessary. Understanding the permitted connection arrangements can simplify piping layouts and reduce installation costs.
Reference: NFPA 13:2019 — Sections 16.15.1.3 & 16.15.1.4.
These notes are for design discussion. Always apply the code edition adopted for your project and confirm with the AHJ.