A 1000 GPM fire pump does not automatically require a 10 GPM jockey pump.
The “1% of fire pump capacity” rule is a common rule of thumb, not an NFPA 20 requirement.
NFPA 20 requires:
• Sizing to restore system pressure following allowable leakage and normal pressure drops.
• Capacity not less than the normal leakage rate.
• Discharge pressure sufficient to maintain the desired system pressure.
For aboveground-only sprinkler and standpipe piping, Annex A.4.27.2.2 recommends jockey pump flow below that of a single sprinkler.
An oversized jockey pump could sustain a sprinkler discharge, preventing pressure from reaching the main fire pump’s start setting.
For extensive underground mains, assess allowable leakage using NFPA 24. The Annex also describes a sizing guideline: make up allowable leakage within 10 minutes, or provide 1 GPM, whichever is larger.
Select the jockey pump based on leakage, pressure requirements, and operating sequence—not a percentage alone.
From Chapter 14 of my upcoming fire protection book.
Reference: NFPA 20 (2025), Section 4.27.2.2–4.27.4 and Annex A.4.27.2.2. Annex guidance is explanatory, not mandatory.
These notes are for design discussion. Always apply the code edition adopted for your project and confirm with the AHJ.